Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.3
Permit Number - TC-COM-0924-01750
Review Name: COMMERCIAL REVIEW - FULL REVISION v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2025 | Commercial Building Standard | APPROVED | Structural(S) Reviewer (from previous submittal TUC9601002.092625) Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 9/28/2025 1:50:35 PM Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Approved with Comments Reason: Date Completed : 10/13/2025 9:57:15 AM |
||
| 10/13/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/13/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 10/10/2025 3:58:05 PM E2: 225-amp secondary feeders from new transformer T2 are undersized for the Keyed note #3 to fuse at 400 amps. Coordinate for proper overcurrent protection or upsize feeders and panel as appropriate. Not Addressed |
||
| 10/08/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |