Permit Number: TC-COM-0924-01750
Parcel: 10123516B

Address:
3742 W RIVER RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.3

Permit Number - TC-COM-0924-01750
Review Name: COMMERCIAL REVIEW - FULL REVISION v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2025 Commercial Building Standard APPROVED Structural(S) Reviewer (from previous submittal TUC9601002.092625)
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 9/28/2025 1:50:35 PM


Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Approved with Comments
Reason:
Date Completed : 10/13/2025 9:57:15 AM
10/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/13/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 10/10/2025 3:58:05 PM
E2: 225-amp secondary feeders from new transformer T2 are undersized for the Keyed note #3 to fuse at 400 amps.
Coordinate for proper overcurrent protection or upsize feeders and panel as appropriate. Not Addressed
10/08/2025 PDSD Application Completeness Express REVIEW COMPLETED