Permit Number - TC-COM-0924-01750
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/10/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/10/2026 | Air Balancing/Commissioning Report (Deferred Submittal) Expressr | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0924-01750 ADDRESS/PARCEL: 3742 W RIVER RD TUCSON, 85741 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. For RTU-8, the outside air CFM appears to be incorrect. It is significantly larger than the design outside air CFM and the outside air and return air CFM is larger than the overall supply CFM. Please correct. |
||