Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.2
Permit Number - TC-COM-0924-01750
Review Name: COMMERCIAL REVIEW - FULL REVISION v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/29/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/29/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 9/28/2025 1:50:35 PM Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 9/27/2025 11:08:10 PM 1. G102 / Egress Plan – Level 1 / Missing revised egress plan. Provide means of egress plan (life safety plan) accordance with 2018 IBC Chapter 10. Revised design shows different ramps and access doors locations. 2. Detail 7 of A421 / Ramp Section / Missing support of ¾” Plywood Ramp. Support system of 5 feet wide ¾” plywood is not specified. 3. Detail 7 and 8 of A501 / Ceiling Joist Details / Missing revised structural sheet. Previous details noted “Plywood Sheathing a per structural” but this revised structural drawing is missing from revised submission. Please provide coordinated revised set, typical. |
||
| 09/29/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 9/26/2025 6:09:35 PM E2: 225-amp secondary feeders from new transformer T2 are undersized for the Keyed note #3 to fuse at 400 amps. Coordinate for proper overcurrent protection or upsize feeders and panel as appropriate. |
||
| 09/09/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |