Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.2

Permit Number - TC-COM-0924-01750
Review Name: COMMERCIAL REVIEW - FULL REVISION v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/29/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 9/28/2025 1:50:35 PM

Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 9/27/2025 11:08:10 PM
1. G102 / Egress Plan – Level 1 / Missing revised egress plan. Provide means of egress plan (life safety plan)
accordance with 2018 IBC Chapter 10. Revised design shows different ramps and access doors locations.
2. Detail 7 of A421 / Ramp Section / Missing support of ¾” Plywood Ramp. Support system of 5 feet wide ¾” plywood is
not specified.
3. Detail 7 and 8 of A501 / Ceiling Joist Details / Missing revised structural sheet. Previous details noted “Plywood
Sheathing a per structural” but this revised structural drawing is missing from revised submission. Please provide
coordinated revised set, typical.
09/29/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 9/26/2025 6:09:35 PM
E2: 225-amp secondary feeders from new transformer T2 are undersized for the Keyed note #3 to fuse at 400 amps.
Coordinate for proper overcurrent protection or upsize feeders and panel as appropriate.
09/09/2025 PDSD Application Completeness Express REVIEW COMPLETED