Permit Number: TC-COM-0924-01747
Parcel: 128100530

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0924-01747
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2024 Commercial Mechanical APPROVED
09/23/2024 Commercial Plumbing APPROVED
09/23/2024 Site Zoning APPROVED
09/25/2024 Site Engineering NOT REQUIRED
09/25/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/23/2024 Commercial Building REQUIRES RESUBMIT For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments followed by the initials (BM)
1. Sheet A1.1 Life safety plans identifies exiting path to restrooms, Direction arrow on plan is identifying a different path. Clarify and correct and also identify second exit route on plans. 2018 IBC 1016 (BM)
2. Sheet A1.1 Clarify space identified as supply, egress exiting through intervening spaces needs to comply with 2018 IBC 1016.2. storage areas or similar spaces shall not be used to pass through. (BM)
09/23/2024 Commercial Electrical REQUIRES RESUBMIT 1. Sheet E3.0 Provide an exit sign at door 108A to comply with 1013.1 for intervening means of egress door within exit. (BM)
2. Sheet E3.0 Should provide a means of egress EM light fixture in area near exit door to comply with 2018 IBC 1008. (BM)
09/16/2024 Fire New Construction REQUIRES RESUBMIT -It appears the "supply" room will be used for storage. Exiting cannot be through a storage room, IFC 1016.2. Please explain.
john.vincent@tucsonaz.gov
5203495581
09/10/2024 PDSD Application Completeness REVIEW COMPLETED