Permit Number: TC-COM-0924-01746
Parcel: 128100530

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0924-01746
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2024 Site Zoning APPROVED
09/26/2024 Site Engineering NOT REQUIRED
09/26/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/23/2024 Commercial Building REQUIRES RESUBMIT For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments followed by the initials (BM)
1. Sheet A1.1 Life safety exiting plan identifies one exiting path to restrooms with direction arrow. Will need to correct to comply with 2018 IBC 1016. (BM)
09/23/2024 Commercial Electrical REQUIRES RESUBMIT Sheet E3.0 Should add exit sign at second exit door as identified on Life safety and exiting plan. Incomplete 2018 IBC107.2.1 & 1013.1 (BM)
09/23/2024 Commercial Mechanical REQUIRES RESUBMIT Sheet M0.0 Reflective ceiling plan identifies mechanical SA and RA in new break room. Mechanical plan does not identify any SA or RA. Clarify 2018 IBC 107.2.1 (BM)
09/23/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Sheet A2.0 New plumbing at break room appears to be placed in stair enclosure wall. Will need to verify fire rating of wall and provide details and penetration data to maintain fire rating and comply with 2018 IBC 714. (BM) Note: will need to address floor penetrations for rated floor assemblies as applicable
09/16/2024 Fire New Construction REVIEW COMPLETED
09/10/2024 PDSD Application Completeness REVIEW COMPLETED