Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0924-01729
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/12/2024 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT The air balance report shows that some of the second floor VAV boxes are operating more that 10% below the specified maximum flowrate. The engineer of record shall review the situation and determine the course of action prior to the air balance report being resubmitted. Reference: Section 403.3.1.5, IMC 2018.
11/12/2024 PDSD Application Completeness REVIEW COMPLETED