Permit Number: TC-COM-0924-01728
Parcel: 10608002C

Address:
835 W PRINCE RD

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0924-01728
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2024 Water - PDSD APPROVED
N/A Bldg Permits - Post Review PENDING ASSIGNMENT
N/A Site Engineering PENDING ASSIGNMENT
09/23/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 9/20/2024 7:28:38 PM





Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Approved
Reason:
Date Completed : 9/7/2024 11:54:58 PM






Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 9/20/2024 4:07:27 PM
1. General - Provide Heat Load calculations. Include total Cooling load. Include all cooling. Separate by zone. Separate by unit types - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads.
2. General - Provide Exhaust/Mechanical Ventilation/Makeup Air to Laundry and Maintenance areas. - 2018 IMC 403.1 Ventilation system. - 2018 IMC 504.6 Makeup air. - 502.1 General.
3. Plan Sheet M2.1 - Because of the higher than normal temperatures in the summer and the extremely cold temperatures in the winter, Natural ventilation is not allowed in Tucson, Arizona. Operable openings will not be opened for ventilation by the occupants. - Authority Having Jurisdiction - 2018 IMC Section 403 Table 403.3.1.1 -
ASHRAE
4. Plan Sheet M2.1 - Include in the COMcheck Mechanical Compliance Certificate all HVAC equipment. (mini-splits and PTAC units) - 2018 IECC Section C403.3.2 HVAC equipment performance requirements.





Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 9/12/2024 2:40:16 PM





Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 9/21/2024 4:03:12 PM
First Plumbing Review:
1). Plan page P1.3: Triple Washers missing LINT interceptor(s). Add lint interceptor due to multiple washers -2018 IPC 1003.6
2)-Plan Page A5.0: Missing Gutter & downspout sizing calculations: Add gutter & downspout sizing calculations. -2018 IPC 1106.3, 1106.6
3). Plan Plan page M1.1: Missing makeup/combustion air for gas dryers. Provide gas combustion Air illustrations & info for laundry room. -2018 IFGC 304
4). Plan Pages P1.3 & C5.0: These plan pages don't correlate as far as the Potable & Fire water mains bldg entrance locations. Update these plan pages to correlate. -2018 IPC 106.3.1
10/02/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review
PROJECT:
TC-COM-0924-01728 - TD-DEV-0924-00246
835 W. Prince Rd., Tucson, AZ 85705
Multifamily Building with Clinic (1st Review)

TRANSMITTAL DATE: October 2, 2024
Please resubmit revised drawings detailed response letter, which states how all Zoning Review Section comments were addressed.
This site is located in the C-2 zone (UDC 4.7.21). Multifamily development is a permitted use in this zone (Table 4.8-4). Medical service-outpatient, excluding blood donor centers, is a permitted use in this zone subject to use-specific standards 4.9.4.O.2 and 4.9.13.P.
Zoning has reviewed the building plans for compliance with development package (DP) TD-DEV-0924-00246 and although it appears that the building plans match, until the DP is approved by all review agencies, Zoning cannot approve this building plan. Please ensure any changes made to the DP prior to approval are reflected on resubmitted building plans.
If you have any questions about this transmittal, please contact Fernando Garcia at fernando.garcia2@tucsonaz.gov.
10/03/2024 Fire New Construction REVIEW COMPLETED
09/06/2024 PDSD Application Completeness REVIEW COMPLETED