Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0924-01721
Parcel: 117160330

Address:
75 E ALAMEDA ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0924-01721
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2024 Site Engineering APPROVED
10/04/2024 Site Zoning APPROVED
10/09/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/23/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 9/22/2024 3:56:53 PM




Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Denied
Reason:
Date Completed : 9/12/2024 4:46:25 AM
1. Sheet A-2.0 and A-3.1 – Show roof access location and method. 2028 International Mechanical Code section 306.1 requires appliances shall be accessible for inspection, service, repair and replacement.
2. Sheet A-3.1 and A-4.0 – Roof edge / Gutter detail is shown but vertical downspout locations are missing (2018 IPC section 1106.3). Downspout support details are missing too.
3. Sheet ME-3.1 – Note 21 states to set existing supports on new roof curbs, refer to Architectural drawings for additional information but it’s missing from Architectural. Cross reference details for clarification in sheet A-3.1, typ.
4. Sheet ME-3.1 – Note 4 provides several new added circuits but missing electrical panel schedule to show capacity of existing electrical distribution panel.






Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 9/23/2024 9:46:03 AM






Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 9/16/2024 8:29:23 AM






Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 9/10/2024 10:46:11 PM
First Plumbing Review: OK Subject To Field Inspections
09/09/2024 PDSD Application Completeness Express REVIEW COMPLETED