Permit Number: TC-COM-0924-01717
Parcel: 22017001B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0924-01717
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/16/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
1 Please provide a narrative or more detail as to the scope of electrical work for this permit. Explain exactly what equipment is connected to temporary power. Provide for OSHA required 'Lock Out-Tag Out' safety procedures for utilizing Temporary power on the premises. All temporary installations shall comply with NEC art 590.
Ref; 2018 IBC section 107.2.1, 2017 NEC
09/10/2024 PDSD Application Completeness Express REVIEW COMPLETED