Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0924-01708
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/08/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
01/08/2025 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Deferred Submittal - Shelving Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 1/8/2025 12:49:09 PM Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 1/6/2025 1:13:35 AM 1. Storage layout shown in A00.3 code plan does not match partial floor plan and shelving layout in SH-1. Provided coordinated and updated A00.3. 2. 2018 IFC section 3201.2 listed item 9 shows to locate required fire department access doors. Show this in SH-1 and updated A00.3. 3. Show exit door swings in A00.3 and SH-1. 2018 IBC section 1010.0.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel were serving a room or area containing an occupant load of 50 or more persons or a group H occupancy. |
||