Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL POOLS v.1
Permit Number - TC-COM-0923-02294
Review Name: COMMERCIAL POOLS v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/12/2023 | Commercial Building | APPROVED | |||
10/05/2023 | Site Zoning | APPROVED | |||
10/12/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
10/12/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1.REf; Plan sheet 2.0. Key Note #1 call out Panel āPā. Could not locate panel āPā. Please clarify. 2. Provide Ground Fault protection for the pool and spa pumps. NEC 680.21(C). 3.Show the location of the Electrical Maintenance shut off switch or provide on the electrical pool plan. NEC 680.13. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
09/28/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |