| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/04/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/04/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. The elevation drawing shows B Meter merging into C Meter, and the Description of Work note #2 states B meter into A Meter. Please clarify. 2. Show the locations of the electrical service(s) and the panels in the electrical plan. 3. Show wiring methods utilized for the merging of the 2 meters. Ref; 2018 UBC section 107.2.1, 2017 NEC. |
||