Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Permit Number - TC-COM-0923-02267
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/31/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/31/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The balance report shows that RTU-1 has only 49% of the required outside air and RTU-2 has only 69% of the required outside air. | ||
| 07/30/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |