Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0923-02267
Parcel: 12513015B

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TC-COM-0923-02267
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/31/2024 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT The balance report shows that RTU-1 has only 49% of the required outside air and RTU-2 has only 69% of the required outside air.
07/30/2024 PDSD Application Completeness Express REVIEW COMPLETED