Permit Number: TC-COM-0923-02267
Parcel: 12513015B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0923-02267
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/13/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 2/13/2024 5:17:24 PM
The structural review is approved. Subject to the field inspector's approval.




Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 2/13/2024 5:16:15 PM
The building review is approved. Subject to the field inspector's approval



Mechanical(M) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 2/13/2024 5:17:00 PM
The mechanical review is approved. Subject to the field inspector's approval.




Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Approved
Reason:
Date Completed : 2/13/2024 5:16:37 PM
The electrical review is approved. Subject to the field inspector's approval.




Plumbing(P) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 2/13/2024 5:15:21 PM
1) Resolved - Sheets P100 (Plumbing Details), I401, I402: Provide the drainage fixture unit calculations for the correct DWV pipe sizing. (2018 IPC section 709.1) Drainage fixture unit calculations do not match the provided and required plumbing
fixtures. There are two water closets shown on the plans and the minimum required two lavatories are to be located in the toilet facilities. Include the accessibility details for all accessories and lavatories in the revised toilet facility design.

2) Resolved - Sheet P100 (Plumbing Details): Include the faucet details meeting the requirements of the amended 2018 IPC sections 412.11 and 419.6 for automatic faucets. Faucet details not provided.

3) Resolved - Sheet P100 (Plumbing Details): Provide the water heater and support drawings and details. (2018 IBC section 107)

4) Unresolved – Sheets P102, P302: The existing grease interceptor listed appears to be a hydromechanical type of grease interceptor (no additional details provided). The amended 2018 IPC section 1003.3 prohibits hydromechanical grease
interceptors being used for more than 4 fixtures. Please provide a letter from the building official if the amended grease interceptor requirements are being waived.
02/13/2024 PDSD Application Completeness Express REVIEW COMPLETED