Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.5
Permit Number - TC-COM-0923-02262
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/02/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. The minimum size for a vent is one-half of the diameter of the drain served (i.e. the downstream vent must be 2”). This will also increase the size of the vent downstream of the vent from GT-1 to 2”. Reference: Section 906.1, IPC 2018. [Second comment: Provide a downstream vent for the grease interceptor. Reference: Section 1003.9, IPC 2018] [Initial comment: Verify if an existing grease interceptor is currently in place to prevent the discharge of fats, oil, and grease into the public sewer. If a grease interceptor is not in place, show how the public sewer is to be protected from harmful discharges. Reference: Section 1003.1, IPC 2018.] 2. Correct the drain sizes shown in detail 5/P1 that do not correspond to the waste sizes shown in the Plumbing Fixture Schedule. |
||
| 04/02/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |