Permit Number: TC-COM-0923-02259
Parcel: 10120033G

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0923-02259
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2023 Water - PDSD APPROVED MASTER SET LOCATED AT: TC-COM-0923-02153 (4995 N CASA GRANDE HY TUCSON, AZ 85743) Bldg 1 & 3 (Outbuilding), Studio Session 394-308-094 WITH REVIEW NOTES TO BE COPIED ON TC-COM-0923-02259 (4985 N CASA GRANDE HY TUCSON, AZ 85743)
10/24/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT MASTER SET LOCATED AT: TC-COM-0923-02153 (4995 N CASA GRANDE HY TUCSON, AZ 85743) Bldg 1 & 3 (Outbuilding), Studio Session 394-308-094 WITH REVIEW NOTES TO BE COPIED ON TC-COM-0923-02259 (4985 N CASA GRANDE HY TUCSON, AZ 85743)
09/25/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/8/2023 11:40:10 PM


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 10/8/2023 11:32:36 PM
1. Sheet G-002b: The code review does not provide a a construction type of the existing building. Provide the applicable construction type for this project in accordance with 2018 IBC Chapter 6.

2. Sheet A-002: UL fire resistance rated assemblies typically are comprised of proprietary materials to achieve a complete assembly. Revise the entire assembly (UL U263) on this sheet to reflect the current assembly listed by UL. The current UL listed assembly is dated August 16, 2023.

3. General: At least 5% of each type of locker is required to be accessible. Provide the proper number of accessible lockers in accordance with the 2010 ADAAG Section 222.1.

4. General: Benches are required to be provided in lockers rooms that comply with Section 903 (2018 IAC) in accordance with the 2010 ADAAG Section 803.4.



Mechanical(M) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 10/8/2023 11:38:30 PM
1. General: Prepare mechanical calculations to show that outside air and other ventilation requirements are met and balanced. Include a ventilation schedule to drawings. Reference 2018 IMC Section 403.1 and Table 403.3.



Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 10/8/2023 11:39:39 PM


Plumbing(P) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 10/8/2023 11:34:58 PM
1. General: The construction plans shall include for each floor level a riser diagram of the plumbing water and waste piping work. The construction plans shall indicate the direction of flow, all pipe sizes, grade of horizontal piping, loading, and location of fixtures and appliances. Please provide a riser diagram for each plumbing system, including gas piping if part of the project. Reference 2018 IPC Section 316.1.4.
10/18/2023 Site Engineering REQUIRES RESUBMIT See Zoning comment
10/13/2023 Site Zoning REQUIRES RESUBMIT MASTER SET LOCATED AT: TC-COM-0923-02153 (4995 N CASA GRANDE HY TUCSON, AZ 85743) Bldg 1 & 3 (Outbuilding), Studio Session 394-308-094 WITH REVIEW NOTES TO BE COPIED ON TC-COM-0923-02259 (4985 N CASA GRANDE HY TUCSON, AZ 85743)


ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0923-02259
4975 E. Benson Hy. – I-1/I-2
Automotive Washing - Self Service (1st Review)

TRANSMITTAL: October 13, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in I-1/I-2 (UDC 4.7.29 & .30), Construction Material Sales is a permitted use in the zone (UDC Table 4.8-5), subject to 4.9.13.Q.

1. As development package (DP), TD-DEV-0923-00388, has not completed its 1st review Zoning is not able to review the building permit for compliance with the DP and will review on the next submittal. Zoning cannot approve the building plans until the DP is approved by all review agencies.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
10/20/2023 Fire New Construction REVIEW COMPLETED MASTER SET LOCATED AT: TC-COM-0923-02153 (4995 N CASA GRANDE HY TUCSON, AZ 85743) Bldg 1 & 3 (Outbuilding), Studio Session 394-308-094 WITH REVIEW NOTES TO BE COPIED ON TC-COM-0923-02259 (4985 N CASA GRANDE HY TUCSON, AZ 85743)
09/22/2023 PDSD Application Completeness Express REVIEW COMPLETED