Permit Number: TC-COM-0923-02245
Parcel: 130056900

Address:
3051 E 36TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.5

Permit Number - TC-COM-0923-02245
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2024 Commercial Mechanical APPROVED
12/17/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/17/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 REF; plan sheet E2.0. The panel schedule for panel ā€˜D’ shows a 100 amp Main Breaker. The load (see load calcs) exceeds the rating of the breaker. NEC art 240, and 408.

2 The Service Electrical Line Diagram shows 200A for new panel ā€˜D’. Is this the rating of the panel? If yes, please reflect this on the panel schedule.

REF; 2018 IBC section 107.2.1, 2017 NEC
12/02/2024 PDSD Application Completeness Express REVIEW COMPLETED