Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.5
Permit Number - TC-COM-0923-02245
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/09/2024 | Commercial Mechanical | APPROVED | |||
12/17/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
12/17/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 REF; plan sheet E2.0. The panel schedule for panel āDā shows a 100 amp Main Breaker. The load (see load calcs) exceeds the rating of the breaker. NEC art 240, and 408. 2 The Service Electrical Line Diagram shows 200A for new panel āDā. Is this the rating of the panel? If yes, please reflect this on the panel schedule. REF; 2018 IBC section 107.2.1, 2017 NEC |
||
12/02/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |