Permit Number: TC-COM-0923-02240
Parcel: 11452008H

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0923-02240
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2023 Site Engineering APPROVED
10/31/2023 Site Zoning APPROVED
11/06/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/24/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/24/2023 12:14:30 PM
See the building review comments.




Building(B) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/24/2023 12:13:39 PM
1) General: Include the drawings for the vehicle impact protection. (2017 NEC section 110.27(B))

2) Development Sheets: Sheets do not have a valid seal. The seals on the two development sheets with charging station details have seals that expired 6/30/23. (2018 IBC section 107)

3) Sheets E0.0 and E2.0: Only one branch circuit is show supplying each dual outlet station. Each outlet requires a separate circuit. Please revise all affected sheets. (2017 NEC section 625.40)


Mechanical N/A


Electrical(E) Reviewer
Keith Miller
kmiller@safebuilt.com
Denied
Reason:
Date Completed : 10/24/2023 12:14:11 PM
See the building review comments.





Plumbing N/A
10/17/2023 PDSD Application Completeness Express REVIEW COMPLETED