Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0923-02240
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2023 | Site Engineering | APPROVED | |||
| 10/31/2023 | Site Zoning | APPROVED | |||
| 11/06/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/24/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 10/24/2023 12:14:30 PM See the building review comments. Building(B) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 10/24/2023 12:13:39 PM 1) General: Include the drawings for the vehicle impact protection. (2017 NEC section 110.27(B)) 2) Development Sheets: Sheets do not have a valid seal. The seals on the two development sheets with charging station details have seals that expired 6/30/23. (2018 IBC section 107) 3) Sheets E0.0 and E2.0: Only one branch circuit is show supplying each dual outlet station. Each outlet requires a separate circuit. Please revise all affected sheets. (2017 NEC section 625.40) Mechanical N/A Electrical(E) Reviewer Keith Miller kmiller@safebuilt.com Denied Reason: Date Completed : 10/24/2023 12:14:11 PM See the building review comments. Plumbing N/A |
||
| 10/17/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |