Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0923-02239
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/02/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/02/2026 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | 1. Verify the exhaust airflow rates for exhaust fans EF-3 through EF-25. Reference: Section 403.3.1.5, IMC 2018. 2. Verify the ventilation airflow rates for the split-system heat pumps FC-6 though FC-11. Reference: Section 403.3.1.5, IMC 2018. 3. Verify the ventilation airflow rates for the split-system heat pumps serving the dwelling units. Reference: Section 403.3.1.5, IMC 2018. 4. Retest the ventilation airflow rate for FC-5 after the under-sized outside air duct has been replaced with an appropriately sized duct. Reference: Section 403.3.1.5, IMC 2018. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 02/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |