Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0923-02227
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/21/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. The site map submitted doesn't show anything but buildings in the general area of the building(s) associated with this application. Show the location of the building(s). 2. Provide a detailed description of the nature or scope of work proposed. “Electrical Reconnect for main building electric meters”. Not specific enough. How many Meters/Buildings are requested to be reconnected, what are their addresses or suite numbers. 3. Why was the power shut off? Ref; 2018 IBC section 107.2.1, |
||