Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.5
Permit Number - TC-COM-0923-02209
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2024 | Commercial Building | APPROVED | |||
| 03/15/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/14/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Previous electrical plan review comments not addressed. Previous comment #1.” Designate branch circuits and panel for all electrical devices, outlets and lighting and correlate with a complete panel schedule.” This means show the branch circuit # and panel designation next to each device. The Branch circuit # must correlate with the panel schedule. Previous comment #3. “Provide compliance with NEC 517.13 where applicable.” Per NEC 517.13 , any areas considered patient care areas including exam room must meet the wiring methods qualified as to provide redundant grounding, Romex (NM) cables and similar not allowed. All wiring in these areas must be installed in metallic conduit or an approved AC type cable. 2 This is a commercial project. Remove all references to the IRC. The 2017 NEC is the applicable electrical Code. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 02/14/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |