Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0923-02209
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/09/2024 Commercial Building REQUIRES RESUBMIT Aloha John, thank you for resubmitting your documents. I was able to insert your permit in between my other reviews. Your email mentioned that you submitting a complete set of construction drawings. However we received on sheet A-1, the rest are missing. Please submit a complete set of drawings.
02/09/2024 Commercial Electrical REQUIRES RESUBMIT The previous electrical plan review comments are not addressed. There was no response submitted for the electrical plan review comments. Previous electrical plan review comments 10-5-23; Please address the electrical plan review comments and provide a written response. 1. Designate branch circuits and panel for all electrical devices, outlets and lighting and correlate with a complete panel schedule. NEC art 408.4 2. Show the location of the breaker panel associated with this project. 3. Provide compliance with NEC 517.13 where applicable. Ref; 2018 IBC section 107.2.1, 2017 NEC.
02/06/2024 PDSD Application Completeness Express REVIEW COMPLETED