Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2023 Commercial Structural APPROVED
09/14/2023 Site Zoning APPROVED
09/14/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Reference; Plan Sheet E-1.

(a) Identify all the overcurrent devices in the Generator and Transfer Switch on the plans.

(b) Show any exterior grounding for the Generator if applicable.

Ref; 2018 IBC section 107.2.1, 2017 NEC
09/15/2023 Fire New Construction REVIEW COMPLETED