Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0923-02205
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/22/2023 | Commercial Structural | APPROVED | |||
09/14/2023 | Site Zoning | APPROVED | |||
09/14/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Reference; Plan Sheet E-1. (a) Identify all the overcurrent devices in the Generator and Transfer Switch on the plans. (b) Show any exterior grounding for the Generator if applicable. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
09/15/2023 | Fire New Construction | REVIEW COMPLETED | |||
09/14/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |