Permit Number: TC-COM-0923-02189
Parcel: 13013046A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0923-02189
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/11/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical review comments and provide a written response.
1. Provide a detailed description of the scope of work to be performed. The details submitted state, "Electrical repair in solar meter". and the sketch on notebook paper shows replacing a 4/0 neutral... Re-submit a more professional electrical plan and detailed information as to the scope of work...If the plan reviewer is unable to determine that the work meets Code, an electrical drawing sealed by a Electrical Engineer may be required.
Ref 2018 IBC section 107.2.1, 2017 NEC
09/20/2023 PDSD Application Completeness Express REVIEW COMPLETED