Permit Number: TC-COM-0923-02188
Parcel: 133110190

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0923-02188
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/20/2023 Commercial Mechanical REQUIRES RESUBMIT The submitted heating/cooling load calculations show a total cooling load of 3.4 tons for the vestibule but the proposed rooftop unit has a 10-ton cooling capacity. How is this justified? [Initial comment: Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed Reference: Sections C403.3.1 and C403.2.2, IECC 2018.]
11/13/2023 PDSD Application Completeness Express REVIEW COMPLETED