Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0923-02188
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/20/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/20/2023 | Commercial Mechanical | REQUIRES RESUBMIT | The submitted heating/cooling load calculations show a total cooling load of 3.4 tons for the vestibule but the proposed rooftop unit has a 10-ton cooling capacity. How is this justified? [Initial comment: Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed Reference: Sections C403.3.1 and C403.2.2, IECC 2018.] | ||
| 11/13/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |