Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0923-02188
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/13/2023 | Commercial Electrical | APPROVED | |||
| 09/18/2023 | Commercial Structural | APPROVED | |||
| 09/18/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/13/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed Reference: Sections C403.3.1 and C403.2.2, IECC 2018). 2. A boxed note on sheet M1.0 and detail 01/M3.0 both call for all of the replacement rooftop units to be connected to existing gas lines but the new units have electric heat. Coordinate the notes. 3. Provide justification for the alternative ventilation calculations. Reference: Section 403.2 (exception), IMC 2018. |
||
| 09/11/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |