Permit Number: TC-COM-0923-02188
Parcel: 133110190

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - TC-COM-0923-02188
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/16/2024 Commercial Mechanical REQUIRES RESUBMIT Per Section C403.3.1, IECC 2018, “The output capacity of heating and cooling equipment shall be not greater than that of the smallest available equipment size that exceeds the loads calculated in accordance with Section C403.1.1.” Based on your documentation, it appears that the 7.5-ton unit is the smallest equipment that will exceed your calculated load. Resubmit the drawing set showing a 7.5 ton unit for RTU02 serving the vestibule. [Second comment: The submitted heating/cooling load calculations show a total cooling load of 3.4 tons for the vestibule but the proposed rooftop unit has a 10-ton cooling capacity. How is this justified?] [Initial comment: Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed Reference: Sections C403.3.1 and C403.2.2, IECC 2018.]
01/12/2024 PDSD Application Completeness Express REVIEW COMPLETED