Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0923-02180
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/09/2023 | Water - PDSD | APPROVED | |||
10/09/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
09/27/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Daljit Benipal dbenipal@safebuilt.com Denied Reason: Date Completed : 9/26/2023 5:10:18 PM 1. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 9/20/2023 3:03:06 PM Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 9/25/2023 11:48:24 PM Provide AHU-ED-East tie down design drawing 2018 IMC 301.15 & 301.18 Provide VAV installation detail 2018 IBC Section [A]107.2.1 Information on construction documents. Provide location of Duct Smoke Detectors on AHU-ED-East on Plan Sheet M-102 2018 IMC 606.2.1 and Section [A]107.2.1 Information on construction documents Provide Condenser tie down design drawing 2018 IMC 301.15 & 301.18 Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 9/25/2023 11:21:29 AM Electrical Review of Medical Center By: Ron Ross PE E-232 SECOND FLOOR PLAN - MECHANICAL POWER: Need to show existing or provide weather proof GFI service receptacles per NEC 210.63 ie several units do not have a service receptacle within 25 feet. E-241 FIRST FLOOR PLAN - FIRE ALARM: Could not locate Key Note 1. E-401 ENLARGED PLANS - POWER: Several details need to use GFI receptacles to comply with NEC 210.8 E-802 ONE-LINE DIAGRAM - ESSENTIAL: Need to provide conductor and conduit size for Panel DR4A-LEB. EA0.1 SCHEDULES, LEGENDS AND GENERAL NOTES - ELECTRICAL: Missing from set. EA0.2 ELECTRICAL SPECIFICATIONS: Missing from set. EA0.3 ELECTRICAL SPECIFICATIONS: Missing from set. EA1.1 FIRST FLOOR ANNEX PLAN - LIGHTING DEMOLITION: Missing from set. EA1.2 FIRST FLOOR ANNEX PLAN - POWER DEMOLITION: Missing from set. EA1.3 ANNEX ROOF PLAN - POWER DEMOLITION: Missing from set. EA1.4 FIRST FLOOR ANNEX PLAN - FIRE ALARM DEMOLITION: Missing from set. EA2.1 FIRST FLOOR ANNEX PLAN - LIGHTING: Missing from set. EA3.1 FIRST FLOOR ANNEX PLAN - POWER: Missing from set. EA3.2 ANNEX ROOF PLAN - POWER: Missing from set. EA4.1 FIRST FLOOR ANNEX PLAN - FIRE ALARM: Missing from set. EA5.1 PANEL SCHEDULES – ELECTRICAL: Missing from set. T201B LEVEL 01 PLAN - TECHNOLOGY - AREA B: Could not locate Keynote 3. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 9/24/2023 11:33:44 PM First Plumbing Review: 1). Add GPM load notation to the 3" roof drains on plan page P-202 -IPC 1106.2 2), S-1 sink in room 12305 needs hot water on plan page P301 IPC 607.1 3). Label the hot piping runs more often throughout plan page P301 -IPC 106.3.1 4).Where will be Vacuum pump drain be discharging?, note 6 on plan page P-403 states pipe drain to edge of house keeping pad, page P-202 does not show a drain in that area. - -IPC 106.3.1 5). Vacuum exhaust Keynote #4 symbol on plan p-403 is shown in locations on this page next to vacuum lines as well? - NFPA99 6). Med Gas & vacuum lines on plan page P-401 & P-403 are not clear on what is new or existing? -IPC 106.3.1, NFPA99 7). Lavs on Plan page P-002 need ASSE 1070 mixing valves -IPC 419.5 |
||
09/28/2023 | Site Engineering | REQUIRES RESUBMIT | 1. The plans cannot be approved until there is an approved associated development package. Lianne Evans lianne.evans@tucsonaz.gov |
||
10/02/2023 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-COM-0923-02180 5301 E. Grant Rd. – PAD-16 Addition & Remodel of TMC Emergency Department (1st Review) TRANSMITTAL: October 2, 2023 Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the PAD-16 (UDC 4.7.24). Medical Service Major is an allowed use in the PAD. 1. Until TD-DEV-0923-00386 has been accepted for its first review Zoning cannot review the building plans for compliance with the development package (DP). Zoning will review the building plans on the next submittal but cannot approve until the DP has been reviewed and approved by all review agencies. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
09/28/2023 | Fire New Construction | REVIEW COMPLETED | |||
09/08/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |