Permit Number: TC-COM-0923-02180
Parcel: 11012094F

Address:
5301 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0923-02180
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2023 Water - PDSD APPROVED
10/09/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/27/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Denied
Reason:
Date Completed : 9/26/2023 5:10:18 PM
1. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 9/20/2023 3:03:06 PM




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 9/25/2023 11:48:24 PM
Provide AHU-ED-East tie down design drawing 2018 IMC 301.15 & 301.18
Provide VAV installation detail 2018 IBC Section [A]107.2.1 Information on construction documents.

Provide location of Duct Smoke Detectors on AHU-ED-East on Plan Sheet M-102 2018 IMC 606.2.1 and Section [A]107.2.1 Information on construction documents

Provide Condenser tie down design drawing 2018 IMC 301.15 & 301.18




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 9/25/2023 11:21:29 AM
Electrical Review of Medical Center
By: Ron Ross PE
E-232 SECOND FLOOR PLAN - MECHANICAL POWER: Need to show existing or provide weather proof GFI service receptacles per NEC 210.63 ie several units do not have a service receptacle within 25 feet.

E-241 FIRST FLOOR PLAN - FIRE ALARM: Could not locate Key Note 1.

E-401 ENLARGED PLANS - POWER: Several details need to use GFI receptacles to comply with NEC 210.8

E-802 ONE-LINE DIAGRAM - ESSENTIAL: Need to provide conductor and conduit size for Panel DR4A-LEB.

EA0.1 SCHEDULES, LEGENDS AND GENERAL NOTES - ELECTRICAL: Missing from set.

EA0.2 ELECTRICAL SPECIFICATIONS: Missing from set.

EA0.3 ELECTRICAL SPECIFICATIONS: Missing from set.

EA1.1 FIRST FLOOR ANNEX PLAN - LIGHTING DEMOLITION: Missing from set.

EA1.2 FIRST FLOOR ANNEX PLAN - POWER DEMOLITION: Missing from set.

EA1.3 ANNEX ROOF PLAN - POWER DEMOLITION: Missing from set.

EA1.4 FIRST FLOOR ANNEX PLAN - FIRE ALARM DEMOLITION: Missing from set.

EA2.1 FIRST FLOOR ANNEX PLAN - LIGHTING: Missing from set.

EA3.1 FIRST FLOOR ANNEX PLAN - POWER: Missing from set.

EA3.2 ANNEX ROOF PLAN - POWER: Missing from set.

EA4.1 FIRST FLOOR ANNEX PLAN - FIRE ALARM: Missing from set.

EA5.1 PANEL SCHEDULES – ELECTRICAL: Missing from set.

T201B LEVEL 01 PLAN - TECHNOLOGY - AREA B: Could not locate Keynote 3.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 9/24/2023 11:33:44 PM
First Plumbing Review:
1). Add GPM load notation to the 3" roof drains on plan page P-202 -IPC 1106.2

2), S-1 sink in room 12305 needs hot water on plan page P301 IPC 607.1

3). Label the hot piping runs more often throughout plan page P301 -IPC 106.3.1

4).Where will be Vacuum pump drain be discharging?, note 6 on plan page P-403 states pipe drain to edge of house keeping pad, page P-202 does not show a drain in that area. - -IPC 106.3.1

5). Vacuum exhaust Keynote #4 symbol on plan p-403 is shown in locations on this page next to vacuum lines as well? - NFPA99

6). Med Gas & vacuum lines on plan page P-401 & P-403 are not clear on what is new or existing? -IPC 106.3.1, NFPA99

7). Lavs on Plan page P-002 need ASSE 1070 mixing valves -IPC 419.5
09/28/2023 Site Engineering REQUIRES RESUBMIT 1. The plans cannot be approved until there is an approved associated development package.

Lianne Evans
lianne.evans@tucsonaz.gov
10/02/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0923-02180
5301 E. Grant Rd. – PAD-16
Addition & Remodel of TMC Emergency Department (1st Review)

TRANSMITTAL: October 2, 2023

Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the PAD-16 (UDC 4.7.24). Medical Service Major is an allowed use in the PAD.

1. Until TD-DEV-0923-00386 has been accepted for its first review Zoning cannot review the building plans for compliance with the development package (DP). Zoning will review the building plans on the next submittal but cannot approve until the DP has been reviewed and approved by all review agencies.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/28/2023 Fire New Construction REVIEW COMPLETED
09/08/2023 PDSD Application Completeness Express REVIEW COMPLETED