Permit Number: TC-COM-0923-02180
Parcel: 11012094F

Address:
5301 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0923-02180
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/09/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved with Comments
Reason:
Date Completed : 11/7/2023 5:59:24 PM
1. S001 - DESIGN ASSUMPTIONS: If this addition is impacting the exterior of the building, please provide additional information on the wind design assumptions. Per the 2018 IBC Section 1603, construction documents shall include design wind pressures for exterior component and cladding materials, expressed in pounds per square feet.

2. S301 - MISSING INFORMATION: On Detail 11/S301, please provide a minimum thickness of concrete footing (not called out on plan) and a minimum weld size to connect the HSS stair post to the proposed base plate.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 9/20/2023 3:03:06 PM




Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 11/6/2023 2:48:01 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 11/6/2023 10:15:31 AM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 11/8/2023 9:15:35 PM
Second Plumbing Review: Comment 7 remains
1). Resolved-Add GPM load notation to the 3" roof drains on plan page P-202 -IPC 1106.2

2), Resolved-S-1 sink in room 12305 needs hot water on plan page P301 IPC 607.1

3). Resolved-Label the hot piping runs more often throughout plan page P301 -IPC 106.3.1

4).Resolved-Where will be Vacuum pump drain be discharging?, note 6 on plan page P-403 states pipe drain to edge of house keeping pad, page P-202 does not show a drain in that area. - -IPC 106.3.1

5). Resolved-Vacuum exhaust Keynote #4 symbol on plan p-403 is shown in locations on this page next to vacuum lines as well? -NFPA99

6). Resolved-Med Gas & vacuum lines on plan page P-401 & P-403 are not clear on what is new or existing? -IPC 106.3.1, NFPA99

7). Un-resolved-Lavs on Plan page P-002 need ASSE 1070 mixing valves -IPC 419.5 ( these are public lavatories private would be in an R occupancy such as a hotel room)
12/01/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
11/14/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena

ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0923-02180
5301 E. Grant Rd. – PAD-16
Addition & Remodel of TMC Emergency Department (2nd Review)

TRANSMITTAL: November 14, 2023

Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the PAD-16 (UDC 4.7.24). Medical Service Major is an allowed use in the PAD.

1. Until TD-DEV-0923-00386 has been accepted for its first review Zoning cannot review the building plans for compliance with the development package (DP). Zoning will review the building plans on the next submittal but cannot approve until the DP has been reviewed and approved by all review agencies.

2. Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
11/03/2023 PDSD Application Completeness Express REVIEW COMPLETED