Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/09/2023 | Commercial Mechanical | APPROVED | |||
09/28/2023 | Fire New Construction | NOT REQUIRED | |||
10/10/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/04/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Show branch circuit and panel designation on the plans. NEC ART 408,4 2. Provide a complete panel schedule including load calculations for the panel. 3. Show the location of the panel feeding the exhaust fan on the plans. 4. Provide disconnecting means, overcurrent protection and controls for the exhaust fan. 5. Why does the exhaust fan detail have the note, “FOR REFERENCE ONLY NOT FOR CONSTRUCTION” next to it. Is this not the correct detail for this fan. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
10/10/2023 | Commercial Structural | REVIEW COMPLETED | |||
09/08/2023 | PDSD Application Completeness | REVIEW COMPLETED |