Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0923-02176
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/11/2023 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0923-02176 (4205 E OLD VAIL CONNECTION RD TUCSON, AZ 85756) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Notate the COT adopted code on the plan-set. 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. 2. Demonstrate compliance with NEC 230.2 (Number of Services). Or, Must have written consent from the Building Official through appeal. 3. Provide a complete line diagram, NEC 110.2, 2018 IBC 107.1. 4. Provide electrical load calculations, for both the Existing/Upgraded Service Panel and the New 400A Service Panel, Per NEC 220.40. 5. Provide an electrical riser diagram, 2017 NEC 230.9. Notate the grounding and bonding method, 2017 NEC 250.20(B), 250.24, 250.30(A)(4). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 09/08/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |