Permit Number: TC-COM-0923-02169
Parcel: 10707016E

Address:
1388 W GRANT RD

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0923-02169
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2023 Bldg Permits - Post Review REVIEW COMPLETED
12/08/2023 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 12/6/2023 8:36:45 PM




Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 12/6/2023 9:47:00 AM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 11/6/2023 2:39:02 PM



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 9/24/2023 2:27:33 PM
ELECTRICAL REVIEW CASINO SELF STORAGE
By: Ron Ross PE
E2.0 ELECTRICAL FIRST FLOOR POWER PLAN: Missing Keynote #5.

E2.6 ELECTRICAL SEVENTH FLOOR POWER PLAN: Could not locate Keynote 2.

E3.1 ELECTRICAL FIRE PUMP GENERAL NOTES: Keyed notes do not match detail.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 11/5/2023 5:18:02 PM
Second Plumbing Review: OK
1). Resolved- Any horizontal portions of the 4" storm conductor conveying the 130 GPM roof area shown on plan page P1.7 will need 1/4" slope -IPC 1106.2 (plan Page P4.0 Shows 1/8") ** SEE P1.7**

2). Resolved- Lavatory mixing valve on plan page P0.1 needs to ASSE 1070 type -IPC 419.5
12/01/2023 PDSD Application Completeness REVIEW COMPLETED