Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0923-02158
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/12/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Designate washer and dryer panel, branch circuit numbers, and correlate with the panel schedule. NEC 408.4 2. Provide GFI protection for the washer receptacle. NEC 210.8(A)(10). 3. Provide load calculations for panel ‘A’ including the added loads for the new Washer and Dryer. NEC 220.14. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
| 09/14/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018. 2. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (i.e. water hammer arrestors for clothes washers). Reference: Section 604.9, IPC 2018. |
||
| 09/07/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |