Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0923-02155
Parcel: 140250860

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - TC-COM-0923-02155
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/08/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Indicate conductor sizes, quantities and types for the electrical service riser. It is the responsibility of the electrical contractor to install these conductors as indicated per Engineered plan. The service entrance conductors are to be sized per NEC art 230.23.

2. The scope of work description entered by the applicant states, "pedestal relocation like for like no increase” The electrical plan submitted shows a new 200-amp electrical service and 2 new Mobile Home Pedestals. Please revise the scope of work description to correlate with the electrical plan.

3. Verify the new Mobile Home Pedestals are suitable for use as service equipment as required per NEC art 550.32.

4 Provide a Grounding Electrode System for the new Mobile Home Pedestals as required per NEC art 250.32.

5. Indicate how the electrical service enclosure and Riser conduit are mounted and supported.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
11/02/2023 PDSD Application Completeness Express REVIEW COMPLETED