Permit Number: TC-COM-0923-02144
Parcel: 11301146Z

Address:
1767 E PRINCE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0923-02144
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2023 Site Zoning APPROVED
10/04/2023 Water - PDSD APPROVED
09/22/2023 Site Engineering NOT REQUIRED
10/04/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
09/25/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 9/22/2023 2:33:07 AM
no structural work was indicated as part of this submittal



Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 9/22/2023 2:32:25 AM
Please be advised, the electrical engineers stamp is about to expire and may need to be updated prior to resubmittal.

Please provide the estimated cost for the project.

1. Sheet CV. Update the scope of work to include the new casework, register stations and the new refrigeration coolers. Clarify if the new casework is heated or cooled units, and if any additional electrical or plumbing will need to be modified. (General Comment).

2. Sheet CV. Clarify if there will be any fire sprinkler work required for the reconfiguration of the new drive-up-go space. (General Comment).

3. Sheet ADA01. Remove the non-applicable details or indicate that they are not used on the drawings. There are no new steps, ramps or restrooms being modified as part of this project. Provide accessible height and reach ranges on the drawings for the new casework. (ICCI A117.1- 2009 Section 308.).

4. Sheet A2.01. Provide elevations or manufacture information showing the accessibility requirements for the new register stations as well as the new casework to be installed. Provide dimensions on the plan showing the new casework locations and minimum aisle clearances on the drawings. (General Comment).

5. Sheet A2.11. Provide a finish schedule for the new work and indicate that all interior finishes will be in accordance with 2018 IBC 803.1.



Mechanical N/A



Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Approved
Reason:
Date Completed : 9/22/2023 2:32:36 AM
09/11/2023 Fire New Construction REQUIRES RESUBMIT -Indicate in the code analysis if building has a fire alarm.
-Building fire alarm required per IFC 907.2.7 when OL is 500 or more.
john.vincent@tucsonaz.gov
5203495581
09/06/2023 PDSD Application Completeness REVIEW COMPLETED