Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.5
Permit Number - TC-COM-0923-02135
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.5
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/18/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/18/2023 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0923-02135 (844 S 6TH AV TUCSON, AZ 85701) 3rd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. 1. Per building_official@tucsonaz.gov, the following information is required, IBC section 107.1. 2. Provide documentation showing TEP limits services to 600A. 3. Provide Complete load calculations for the given addressed location showing that the total load required exceeds TEP single service capacity thus requiring a new service. |
||
10/09/2023 | PDSD Application Completeness | REVIEW COMPLETED |