Permit Number: TC-COM-0826-01420
Parcel: 14024079B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0826-01420
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2026 Commercial Electrical APPROVED
09/14/2026 Fire New Construction NOT REQUIRED
09/14/2026 Site Engineering NOT REQUIRED
09/21/2026 Site Zoning NOT REQUIRED
09/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/14/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov

1. Provide structural design calculations for the proposed work. 2024 IBC Section 107.2.1.
2. Identify the equipment requiring the 8-inch-thick floor and indicate its location and design loads on the plans. 2024 IBC Sections 107.2.1 and 1603.1.
3. Provide a clear description and scope of work on the plans, including all proposed construction and equipment installations. 2024 IBC Section 107.2.1.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/04/2026 PDSD Application Completeness Express REVIEW COMPLETED