Permit Number: TC-COM-0826-01418
Parcel: 10612017Q

Address:
1765 W PRINCE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0826-01418
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2026 Site Engineering Standard NOT REQUIRED
09/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/28/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0826-01418
ADDRESS/PARCEL: (1765 W PRINCE RD TUCSON, AZ 85705)
Submit your revised drawings along with a ***detailed response letter***, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. EXISTING DRAWINGS
a. The submitted drawings are the original set of drawings of the previously approved building permit when the structure was first built. It reflects all work that was done at that time.
b. This set of drawings can be submitted as reference only. Please the following note on every sheet: “FOR REFERENCE ONLY”
2. NEW SET OF CURRENT CONDITION DRAWINGS
a. Please submit a set of construction documents that reflects the work actually being done.
i. Please ensure that the drawings are sealed/signed/dated by a licensed Arizona professional such as an Architect, Engineer, etc.
3. Please resubmit.
09/18/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01418 (1765 W PRINCE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide plans relevant to the scope of work being done. Plans must show compliance to the currently adopted codes as listed above. Cannot show old plans.

Additional review and comments will be required when provided sealed plans showing the actual scope of work being done.
09/24/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0826-01418
ADDRESS/PARCEL: 1765 W PRINCE RD TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please provide plans that reflect the current scope of work. The 2012 plans may be used for reference but cannot be used as the current plans for this permit. Please show any proposed mechanical and plumbing work and update the plans to reference the currently adopted City of Tucson codes and amendments. Reference: Section 107.2.1, IBC 2024.
09/24/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0826-01418
ADDRESS/PARCEL: 1765 W PRINCE RD TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please provide plans that reflect the current scope of work. The 2012 plans may be used for reference but cannot be used as the current plans for this permit. Please show any proposed mechanical and plumbing work and update the plans to reference the currently adopted City of Tucson codes and amendments. Reference: Section 107.2.1, IBC 2024.
09/28/2026 Fire New Construction Standard REQUIRES RESUBMIT -See building comments.
john.vincent@tucsonaz.gov
5203495581
09/18/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01418 (1765 W PRINCE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide plans relevant to the scope of work being done. Plans must show compliance to the currently adopted codes as listed above. Cannot show old plans.

Outdoor lighting Review
1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
2. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
3. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
5. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
6. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
7. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.

Additional review and comments will be required when provided sealed plans showing the actual scope of work being done.
09/24/2026 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0826-01418
ADDRESS/PARCEL: 1765 W PRINCE RD TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please provide plans that reflect the current scope of work. The 2012 plans may be used for reference but cannot be used as the current plans for this permit. Please show any proposed mechanical and plumbing work and update the plans to reference the currently adopted City of Tucson codes and amendments. Reference: Section 107.2.1, IBC 2024.
09/04/2026 PDSD Application Completeness Express REVIEW COMPLETED
09/24/2026 Site Zoning Standard REVIEW COMPLETED Proposed scope does not indicate any exterior modifications to the exterior site nor additional building square footage.