Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0826-01409
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2026 | Commercial Electrical Standard | APPROVED | |||
| 09/17/2026 | Outdoor Lighting Standard | APPROVED | |||
| 09/28/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/03/2026 | Addressing Validation | REQUIRES RESUBMIT | For questions: cdrc@tucsonaz.gov The address on the permit is "4440 S CAMPBELL AV," however the address on the plans is "4502 S CAMPBELL AV." The address on the plans must match the address on the permit. Please resubmit documents with matching permit address. OR If the address on the permit is incorrect, please apply for a change of address request to add the correct address. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf Change of address request instructions can be found here: https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/sub-records.pdf |
||
| 09/25/2026 | Commercial Building Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0826-01409 ADDRESS/PARCEL: (4440 S CAMPBELL AV TUCSON, AZ 85714) Submit your revised drawings along with a ***detailed response letter***, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976. COMMENTS: 1. Per the City of Tucson Building Permit Processes and Procedures, this facility requires two building permits. 2. The First permit is for the Canopy Structure along with the Fuel Dispensers, Underground Tanks and related Fuel System. a. Please separate all the information related to the Canopy, Fuel Dispensers and related equipment. Apply and submit for a totally separate building permit. b. Submit the Structural Calculations and Drawings for the Canopy that is sealed/signed/dated by a State of Arizona licenses Structural Engineer. c. Please provide the new canopy/fuel dispenser building permit number as part of your response to the convenience store comments below. 3. The second permit is for the Convenience Store. a. The City of Tucson proposed to use this current building permit TC-COM-0826-01409 for the Convenience Store. b. We will continue reviewing using this current set of drawings (on the COVER SHEET, we will add the note: “This permit TC-COM-0826-01409 is for the Convenience Store ONLY. Please see the separate building permit for the Canopy and Fuel Dispenser System.” c. On the Permit Description, the City will adjust it to: New convenience store ONLY d. At this time, below are the comments the City has about this current Convenience Store drawings. i. SHEET G0.01 APPLICABLE CODES, Correct the cycle year for the National Electrical Code to 2023. Add the ICC A117.1 - 2017 Accessible and Usable Building and Facilities. Add the 2012 City of Tucson/Pima County Outdoor Lighting Code ii. SHEET G0.01 Under Code Summary - EXIT ACCESS TRAVEL DISTANCE: Enter the exit access travel distance allowed for an M occupancy without automatic sprinkler system per IBC 1017. In the Life Safety Plan Sheet G1.01, illustrate that the travel distance is not exceeded. iii. SHEET G0.03 CLEAR FLOOR SPACE: What is shown is a 60” turning space. The turning space shall be a circular space with a 67-inch minimum diameter per ICC A117.1 sec 304.3.1.1 Please correct this. iv. SHEET 2.0 SIGN 04 – BUILDING ELEVATION: Signs are a separate permit from the Convenience Store building permit. Please submit and apply for a separate Sign Permit. v. SHEET 2.0 FUEL CANOPY ELEVATOIN: Signs are a separate permit from the Convenience Store building permit. Please submit and apply for a separate Sign Permit. vi. SHEET A0.01 DUMPSTER ENCLOSURE: Please make the correction. Comply to bollard locations and general requirements of dumpster enclosure using the City of Tucson Unified Development Code using this link: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-11666 vii. SHEET A4.01 RESTROOM ENLARGED PLAN: The turning space is shown as 60”. Please make the correction and show in both the Men’s and Women’s Restrooms. The turning space shall be a circular space with a 67-inch minimum diameter. ICC A117.1 sec 304.3.1.1 viii. SHEET A5.13 DETAIL 7 AND OTHERS: Please ensure to comply to the required clearances for exterior finishes’ bottom of Weep Screed to soil or concrete sidewalks surfaces. The weep screed shall be placed not less than 4 inches above the earth or 2 inches above paved areas and be of a type that will allow trapped water to drain to the exterior of the building per IBC: 2512.1.2. Please correct the drawing to show the 6 inch required clearance for siding, etc. ix. SHEET S0.03 SPECIAL INSPECTIONS: Please provide a special inspection certificate with Part A, and Part B completed with next submittal. Special Inspection(s) Required (Provide table specific to the project) IBC 1705 This form is available in: a.https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-development-services/documents/special_inspection_certificate.pdf b.Ensure that Part B is sealed/signed/dated by the special inspector in charge. Ensure to use Special Inspectors who are active in the approved list of special inspectors. They are available in the following links: i.special-inspectors-by-name.pdf (orovalleyaz.gov) ii.https://content.civicplus.com/api/assets/e426f390-7bd6-4c47-9bc1-357282083afd iii.https://www.phoenix.gov/pddsite/Documents/TRT/dsd_trt_pdf_00870.pdf c. On the Cover Sheet, please list all the special inspections that are required. e. VALUATION is shown as $1,500,000. Please separate the valuation between the Convenience Store and the Canopy/Fuel Dispenser. Please provide the appropriate Convenience Store Valuation. Please provide a separate valuation for the Canopy/Fuel Dispenser. These valuations will be entered into their respective building permits. f. Please resubmit. |
||
| 09/24/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0826-01409 ADDRESS/PARCEL: 4440 S CAMPBELL AV TUCSON, AZ 85714 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Please provide heating and cooling load calculations to verify that the proposed HVAC equipment is properly sized for the space. Reference: Section C403.1.1 and C502.3.3, IECC 2024. 2. Show that the walk-in cooler and walk-in freezer comply with the construction and efficiency requirements of Sections C403.12.2 and C403.12.2.1, IECC 2024. 3. The hood section detail on Sheet M1.03 appears to reference EF-3, but EF-2 appears to be the exhaust fan serving the hood. Please correct. Reference: Section 107.2.1, IBC 2024. 4. Please clarify why the mechanical plan (Sheet M1.01) shows the return air CFM for each rooftop unit as equal to the total supply air CFM. For example, RTU-1 is shown with 3,000 CFM supply air and 3,000 CFM return air on the plans, while the air balance shows 2,345 CFM return air after accounting for the 655 CFM of outside air. Please coordinate the mechanical plans and the air balance schedule. Reference: Section 107.2.1, IBC 2024. |
||
| 09/24/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0826-01409 ADDRESS/PARCEL: 4440 S CAMPBELL AV TUCSON, AZ 85714 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. The condensate lines from the refrigerated coolers appear to indirectly discharge into the floor sink connected to the grease waste system. Please clarify the proposed drainage connection for the condensate and provide the code basis for this connection. Additionally, provide the calculations and sizing information for the proposed grease waste system. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson. 2. Please clearly show the size, routing, and termination of the condensate drains from the RTUs. Reference: Section 307.2.1, IMC 2024 as amended by the City of Tucson. 3. Please provide a gas piping layout showing the pipe sizes, developed lengths, and total connected gas load to verify compliance with the 2024 IFGC. Reference: Section 402, IFGC 2024. |
||
| 09/28/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | -Resolve all building comments. -Indicate a CO2 gas detection alarm will be installed per IFC 5307.3. This will be a separate permit through TFD. john.vincent@tucsonaz.gov 5203495581 |
||
| 09/14/2026 | Site Engineering Standard | REQUIRES RESUBMIT | Permit Activity Number: TC-COM-0826-01409 (1st Review) Project: New gas station and convenience store. Location: 4440 S CAMPBELL AV Review Date: 9/14/2026 Reviewer: Marco Contreras – Engineering Associate - Site Engineering Reviewer Contact: Marco.contreras@tucsonaz.gov Related cases: Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering. To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Please do not mark or highlight changes in the drawings at this stage — revision markups are only used after a permit has been issued. Submit your response letter and updated plan set as two separate files. Site Engineering Review Comments: 1. Site Engineering has completed its review of the submitted building plan set and cross-referenced it against the associated Development Package. However, final approval of this Commercial permit cannot be granted until the associated submission of the Development Package TD-DEV-0226-00050 has received full approval and has been issued. Per UDC §3.3.3.G, building permits for sites requiring a Development Package may not be issued prior to DP approval, as the building plans must be consistent with an approved site plan. Please resubmit for final approval once the Development Package has been approved and issued by all applicable reviewers. |
||
| 09/23/2026 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Jeffrey W. Cassidy, Planner I Planning & Development Services Department – Current Zoning Review Section, Commercial PROJECT: TC-COM-0826-01409 – Commercial – New Maverick gas station and convenience store 4440 S CAMPBELL AV TUCSON, AZ 85714 (C-2 Zoning) Commercial Building Plan Review – 1st Review TRANSMITTAL DATE: September 23, 2026 1. COMMENT: Zoning has completed its review of the submitted building plan set and cross-referenced it against the associated Development Package. However, final approval of Commercial Permit TC-COM-0826-01409 cannot be granted until the associated revision to Development Package TD-DEV-0226-00050 has received full approval and has been issued. Per UDC §3.3.3.G, building permits for sites requiring a Development Package may not be issued prior to DP approval, as the building plans must be consistent with an approved site plan. Please resubmit for final approval once the Development Package has been approved and issued by all applicable reviewers. For final approval, ensure the building plans match the approved DP regarding footprint, proposed height, and square footage, and that the downspout and structure drainage systems shown in the building plans are consistent with those depicted in the Development Package plan set. 2. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: 3. COMMENT: Corrected commercial building permit. 4. COMMENT: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home . Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code . |
||
| 09/24/2026 | Water - PDSD Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0826-01409 ADDRESS/PARCEL: 4440 S CAMPBELL AV TUCSON, AZ 85714 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. The development plan (TD-DEV-0226-00050) shows a 2” proposed water meter and the water calculations show a 1-1/2” water meter. Please clarify the proposed water meter size and revise the plans and calculations as necessary to ensure consistency. Reference: Section 107.2.1, IBC 2024. |
||
| 09/03/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |