Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0826-01406
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2026 | Water - PDSD Standard | APPROVED | |||
| 09/16/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 09/16/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 09/28/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/24/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov 1. Structural Calculations: Please revise the Code in the design to reflect the 2024 IBC in place of the 2025 CBC. 2024 IBC 107.2.1 2. Please revise the structural calculations and plans to include the proposed rooftop units (RTUs). The current structural calculations do not appear to evaluate the RTUs or their supporting structure. A. Provide an evaluation of the existing roof framing, supporting members, connections, and attachments for the RTU loads, including applicable dead, live, wind, and seismic loads. Identify the RTU locations on a roof key plan and provide engineered reinforcement or modification details where required. 2024 IBC Sections 107.2.1, 107.2.7, 1604.2, 1605, 1606, 1607, 1609, and 1613. 3. Please update code notes on sheets 10 and 22 to use the IC code references in place of CBC references. 2024 IBC 107.2.1 Please treat this as a typical note for these construction documents. 4. Sheet T1.0: The total design occupant load is stated as 93 under the Occupancy Calculation. However, under the #2. Plumbing Fixture Calculation, the plumbing occupant load factor has been reduced to 83 OCC/2=42 occupants. Further, under the Plumbing Fixture Calculations Table the number of occupants appears to have been reduced to 21 male and 21 female or 42 total occupants. Please revise the number of occupants so consistent information is provided throughout the construction documents. 2024 IBC 107.2.1 Additionally, please use 2024 IPC Table 403.1 Number 1 Assembly/Restaurants 1 factor of 1 per 75 for both Male and Female in place of the existing factors. 5. Sheet A2.0: Fire-retardant-treated (FRT) plywood is combustible and does not become noncombustible by virtue of its treatment. FRT plywood over metal studs does not, by itself, qualify as a noncombustible wall assembly for the Type I hood clearance exception. 6. Provide wall construction details demonstrating compliance with 2024 IMC Section 507.2.6, including required clearances from combustible materials. Where reduced clearance is proposed, provide the required noncombustible wall assembly and noncombustible, smooth, cleanable, nonabsorbent surface extending a minimum of 18 inches in all directions from the hood. Provide the appliance manufacturer's installation instructions/listing and demonstrate compliance with applicable appliance clearances and 2024 IMC/NFPA 96 requirements. 7. Sheet A2.1: Please indicate the individual chairs are fixed as 2024 IBC 1030.9.5 requires dead-end aisles serving fewer than 50 seats comply with 1030.8 which requires fixed seating in these dead-end aisles. Additionally, without fixed seating the aisle width would not be wide enough at 3’8” Please contact me if you have any questions about the above comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 09/16/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0826-01406 (2501 E GRANT RD Unit:UNIT 161 TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. If the registrant is not a registered electrical engineer, the registrant must be qualified to perform such work per A.A.C. R4-30-302 and the electrical work must be incidental to the work of the registrant’s profession for the project per A.R.S. 32-143. (Incidental is defined as minor electrical work that is a result of the work of the registrant’s profession for the project). a. The provided scope of work does not meet the definition of ‘incidental’. The electrical sheets must be sealed by an Arizona Registered Electrical Engineer. 2. Reference sheet E-1.0, under the 'Caution' section. Show all work to comply with the City of Tucson adopted codes and local amendments, https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Building-Codes 3. Reference sheet E-1.1, Single-Line Diagram General Notes: Remove all reference to the 2020 NEC and 2022 CEC and show compliance with the 2023 NEC as adopted by the City of Tucson. 4. Provide conductor sizing within the electrical panel schedules, or provide a general conductor sizing chart. NEC 310.15. 5. Circuit B-14 & B-29 is shown as 'SPARE' in the panel schedule, but Circuit B-14 is shown as a receptacle for item M-2, To-Go-Cabinet and B-29 is shown as a receptacle in the dining area. Please verify and correct. 6. Verify no mechanical or plumbing equipment is withing the dedicated space above the panel. NEC 110.26(E)(1). Reference sheet E-3.0, power plan, tank-less water-heater item 75 is shown above ceiling and overlapping with panel 'M'. 7. Update general electrical note 'n', on sheet E-3.0, to include GFCI for all appliance OUTLETS as listed per NEC 210.8(D). 8. Provide GFCI protection for all receptacles within the buffet serving area around the conveyor. NEC 210.8(B)(4). 9. Provide GFCI protection for all receptacles within the Beverage Station area, room 138. NEC 210.8(B)(3). 10. Reference sheet E-3.0, Electrical Power Keyed Note #1. Show conductors sized per NEC 310.15, and include ampacity adjustment factors for more than three current carrying conductors per NEC 310.15(C). The note for Conductors on sheet E-1.0 indicates that conductors under a #1 AWG size are sized based on the 60 C temperature rating. given 6 current carrying conductors in a single conduit, the #12 Cu, type TW, conductors would be undersized for the 20A OCPDs. |
||
| 09/22/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0826-01406 ADDRESS/PARCEL: 2501 E GRANT RD Unit:UNIT 161 TUCSON, AZ 85716 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Please provide heating and cooling load calculations to justify the heating/cooling capacity of the HVAC Equipment. Reference: Section C403.1.1 and C502.3.3, IECC 2024. 2. Show that the walk-in cooler and walk-in freezer comply with the construction and efficiency requirements of Sections C403.12.2 and C403.12.2.1, IECC 2024. 3. HP-90A appears to be using the hallway as a return air duct. Corridors are not permitted to be used as a return-air path. Please clarify. Reference: Section 601.2, 2024 IMC. |
||
| 09/22/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0826-01406 ADDRESS/PARCEL: 2501 E GRANT RD Unit:UNIT 161 TUCSON, AZ 85716 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. The plumbing riser gas diagram shows 200 feet of 2-1/2" pipe from the gas meter/regulator valve to the first shutoff valve. Based on Table 402.4(2) of the 2024 IFGC, a 3" pipe is required at 200 feet for a demand of 1,410 CFH. Please clarify the proposed pipe sizing. 2. Please verify that the distance from the hot water source to the hot water termination for the lavatory complies with the requirements of Section C404.5, IECC 2024. |
||
| 09/28/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | -Resolve building comments. -Please add kitchen hood suppression system to separate submittals, T1.0 john.vincent@tucsonaz.gov 5203495581 |
||
| 09/24/2026 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: Olga Salazar PDSD Zoning Review Section PROJECT: TC-COM-0826-01406 – Restaurant Tenant Improvement (1st Review) 2501 E Grant Rd Unit 161 TRANSMITTAL DATE: September 24, 2026 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: On the cover sheet, under “Building & Site Data”, please correct the following information: - The zoning classification is C-2 - The Pima County Parcel Number associated to this property is 112-07-168A. - Add a note indicating the existing and proposed use as Food Service – Restaurant, subject to UDC use specific standards 4.9.4.M.1 and 4.9.13.P. 2. COMMENT: The proposed restaurant involves the combination of existing Suites 181 and 161. According to the last approved records (T19CM01535 and T18CM05222), the total gross floor area of Suite 181 is 1,934 s.f., and that of Suite 161 is 1,313 s.f. The combined gross floor area is therefore 3,247 s.f. Please correct the total gross floor area listed under Note “C” under “Building & Site Data”, or clarify this discrepancy. 3. COMMENT: More comments may be forthcoming based on the next submittal's response. If you have any questions about this transmittal, contact Olga Salazar at Olga.Salazar@tucsonaz.gov. |
||
| 09/02/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |