Permit Number: TC-COM-0826-01384
Parcel: 117084100

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0826-01384
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/24/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this Review, please contact
PDSD-Permits@tucsonaz.gov

Please resubmit addressing the following comments
1) Plan/documents need full address, including specific unit number.
08/25/2026 Commercial Mechanical Express REQUIRES RESUBMIT 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacity of the unit being installed (Section C403.3.1, IECC 2024). The unit will also have to comply with Sections C403.2.2, C403.3.2, C403.4 and C403.5, IECC 2024 for efficiency, controls, and economizer. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.3, IECC 2024.
2. Note: New heating /cooling loads are not required for emergency replacement of cooling and heating equipment where there are no alterations, additions, or changes of occupancy, the equipment does not increase in capacity, and the equipment was installed prior to January 1, 2013. Reference: Section C403.1.1, IECC 2024, as amended by the City of Tucson

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
08/24/2026 PDSD Application Completeness Express REVIEW COMPLETED