Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0826-01382
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/02/2026 | Commercial Building | APPROVED | |||
| 10/05/2026 | Site Zoning | APPROVED | |||
| 10/05/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/05/2026 | Commercial Mechanical | REQUIRES RESUBMIT | The City of Tucson did not adopt ASHRAE Standard 62.1 for ventilation calculations and the 2024 IMC only references the ASHRAE Standard for the purpose of calculating the system ventilation efficiency (Ev). Provide calculations to show that the ventilation system is sized in accordance with Section 401.2, IMC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 10/05/2026 | Commercial Plumbing | REQUIRES RESUBMIT | Show how tepid water is provided to the lavatory. Reference: Sections 303.4, 419.5, and 607.1.2, IPC 2024, and Section C404.5, IECC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 10/05/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 09/21/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |