Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2026 Commercial Electrical APPROVED
09/11/2026 Water - PDSD APPROVED
09/09/2026 Site Engineering NOT REQUIRED
09/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/10/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Please provide Design Occupant Load (number of occupants) IBC 1004.1
3. Provide referenced wall section graphically illustrating the wall assembly and top and bottom connections. IBC 107.2.1
4. Please review the stated project valuation of $1500.00. Based on the adopted fee schedule, the project square footage, and classification as a Level 2 alteration area less than 50% of the building), the value derived from the default calculation is much higher than what was specified on the permit application.
Please provide a copy of the construction contract or detailed estimates to verify the project valuation. If additional information is not provided, the permit fees will be assessed based on the calculated valuation in accordance with IBC 109.3 and the adopted fee schedule.

%. Please amend the plans to provide the following Tucson Code Section 7-137 requirements.
(1) A readable sign shall be permanently attached and posted at the main entrance identifying the establishment as a massage establishment. The sign shall not be smaller than three (3) inches by five (5) inches and be of a durable material.
(6) Closed cabinets shall be provided, and used, for the storage of clean linens.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/11/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0826-01382
ADDRESS/PARCEL: 8963 E TANQUE VERDE RD Unit:UNIT 195 TUCSON, AZ 85749

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Due to the proposed change of occupancy, please provide ventilation calculations demonstrating compliance with the minimum outdoor air ventilation requirements for the proposed occupancy. Reference: Section 1008.1, IEBC 2024 & Table 403.3.1.1, IMC 2024
2. There does not appear to be a return register in Massage Room #1, and the hallway is being utilized as the return-air path for this room. Per Section 601.2, corridors shall not be used as return-air ducts. Section 7-137(3) also requires rooms in massage establishments to have a window that opens and/or a supply and return register. Please revise. Reference: Section 601.2, IMC 2024.
09/11/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0826-01382
ADDRESS/PARCEL: 8963 E TANQUE VERDE RD Unit:UNIT 195 TUCSON, AZ 85749

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Plans must be sealed by an Arizona-registered design professional. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Please show compliance with Section 7-137(3), (5) & (11) of the Tucson, Arizona Charter and General Ordinances, for ventilation and plumbing. https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az/0-0-0-5098.
09/10/2026 Fire New Construction REQUIRES RESUBMIT -Please include the occupant load in the code analysis. Include any fire protection systems information.
john.vincent@tucsonaz.gov
5203495581
09/11/2026 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Jeffrey W. Cassidy, Planner I
Planning & Development Services Department – Current Zoning Review Section, Commercial

PROJECT:
TC-COM-0826-01382 – Commercial – Tenant Improvement for Massage (Personal Service) Use
8963 E TANQUE VERDE RD Unit 195 TUCSON, AZ 85749 (C-1 Zoning)
Certificate of Occupancy Review – 1st Review

TRANSMITTAL DATE:
September 11, 2026

1. COMMENT: Update zoning classification from C-2 to C-1.

2. COMMENT: Add the Zoning Use to the TS.1 sheet: Commercial Services Use – Personal Services subject to use specific standards 4.9.4.T.1 and 4.9.13.O.

3. COMMENT: Indicate the vehicle parking required and provided per UDC Table 7.4.4-1.

4. COMMENT: Indicate the bicycle parking required and provided per UDC Table 7.4.8-1.

5. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

6. COMMENT: Corrected commercial building permit.

7. COMMENT: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home .

Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf

If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code .
08/27/2026 PDSD Application Completeness Express REVIEW COMPLETED