Permit Number: TC-COM-0826-01381
Parcel: 13333026B

Review Status: In Review

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0826-01381
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2026 Fire New Construction NOT REQUIRED
09/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/09/2026 Commercial Building PENDING ASSIGNMENT
09/09/2026 Site Engineering PENDING ASSIGNMENT
09/09/2026 Site Zoning PENDING ASSIGNMENT
09/03/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01381 (1051 N HARRISON RD TUCSON, AZ 85748)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide a Grounding Electrode System at the detached structure per 250.31(A), 690.47. Grounding electrode system and grounding electrode conductor. Required.
2. Provide appropriate grounding and bonding of all metal structures, per all relevant sections of NEC 250 (example sections 250.4(A), 250.20, 250,32, 250.104, 690.43.
3. Provide grounding/bonding of the Generac Generator per manufacturer’s requirements and NEC 250.
4. Show the Grounding Conductor’s connection at the modules, mounting and metal support structure. NEC 690.43.
5. Clarify if there is any under canopy lighting going to be installed. Any under canopy lighting to be full cutoff with a maximum color temperature of 3500K. additional outdoor lighting comment may be needed if lighting is installed.
08/27/2026 PDSD Application Completeness Express REVIEW COMPLETED