Permit Number: TC-COM-0826-01347
Parcel: 12702359B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0826-01347
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2026 Commercial Building Standard APPROVED
09/10/2026 Site Engineering Standard APPROVED
09/17/2026 Site Zoning Standard APPROVED
09/17/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/25/2026 Addressing Validation REQUIRES RESUBMIT For questions: CDRC@tucsonaz.gov
Your permit application project address is missing a unit number. To add the unit number, please submit a Request Change of Address. If the address does not appear on the list, please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the unit.
Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
HOW TO SUBMIT A REQUEST CHANGE OF ADDRESS:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf
09/09/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01347 (5447 E 5TH ST TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide a Grounding Electrode System at the detached structure per 250.31(A), 690.47. Grounding electrode system and grounding electrode conductor. Required.
3. Provide appropriate grounding and bonding of all metal structures, per all relevant sections of NEC 250 (example sections 250.4(A), 250.20, 250,32, 250.104, 690.43.
4. Show the Grounding Conductor’s connection at the modules, mounting and metal support structure. NEC 690.43.
5. Detail how the Line-side tap is being done and show this interconnection does not violate the listing of the existing 1200A equipment, NEC 110.3.
6. Provide complete AC Overcurrent Protective Device and Conductor Sizing calculations for PV source Circuits and Module Interconnection Conductors (Imax x 1.25) Reference NEC 690.9(B), 690.8(A) and (B). Show a complete calculation for determining OCPD and conductor requirements.
7. The 3/0 AWG CU conductors, reference IDs 4-6, are undersized for the 400A Fuse in the DG fused disconnect.
09/09/2026 Outdoor Lighting Standard REQUIRES RESUBMIT 1. Clarify if there is any under canopy lighting going to be installed. Any under canopy lighting to be full cutoff with a maximum color temperature of 3500K. Additional outdoor lighting and electrical comments may be needed if lighting is installed.
08/26/2026 Fire New Construction Standard REVIEW COMPLETED
08/25/2026 PDSD Application Completeness Express REVIEW COMPLETED