Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0826-01345
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/21/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01345 (7950 E STELLA RD Unit:BLDG G UNIT 3 TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide Surge Protection as required per 2023 NEC 230.67, NEC 230.67(D).
2. Add each address and unit number to the provided plans.
08/20/2026 PDSD Application Completeness Express REVIEW COMPLETED