Permit Number: TC-COM-0826-01342
Parcel: 140420340

Review Status: Requires Resubmit

Review Details: COMMERCIAL FENCE/WALL v.1

Permit Number - TC-COM-0826-01342
Review Name: COMMERCIAL FENCE/WALL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2026 Commercial Building APPROVED
09/09/2026 Site Engineering APPROVED
09/10/2026 Site Zoning APPROVED
09/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/25/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions about this review contact PDSD@tucsonaz.gov
Project address on permit application does not match address on plans submitted. If the address on the plans is incorrect, please update plans and resubmit. If the permit application address is incorrect, please submit a Request Change of Address to update this application.
Step by Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
How to request a change of address:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf
09/10/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01342 (2620 E AIRPORT DR TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide an electrical panel schedule and designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
2. Provide electrical load calculations, for the Panel, Per NEC 220.40.
3. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
4. Show the burial depth of the new conduit per NEC 300.5.
08/25/2026 PDSD Application Completeness Express REVIEW COMPLETED