Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0826-01328
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/02/2026 | Commercial Building | APPROVED | |||
| 08/31/2026 | Commercial Electrical | APPROVED | |||
| 09/04/2026 | Site Zoning | APPROVED | |||
| 09/08/2026 | Commercial Plumbing | NOT REQUIRED | |||
| 08/26/2026 | Site Engineering | NOT REQUIRED | |||
| 09/08/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/08/2026 | Commercial Mechanical | REQUIRES RESUBMIT | Provide the air rebalancing information for the men’s restroom (110) on sheet M0.04. Reference: Section 107.2.1, IBC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 09/08/2026 | Water - PDSD | REQUIRES RESUBMIT | Show the location and size of the existing water meter and backflow preventer serving this building on a site plan. Reference: Section 107.2.1 and 107.2.6, IBC. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 09/08/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 08/24/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |