Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/31/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0826-01325 (938 N BELVEDERE AV TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The provided aerial view does not match the provided address. Update with correct site.
2. The provided sheet has inconsistent information. Is this a like-for-like replacement or an upgrade/increase in service size? Is it overhead, or underground fed? Only one unit is shown at this address, not 5.
3. Provide Service Surge Protection per NEC 230.67(D). All downstream dwelling units require surge protection when replacing the service equipment.
4. Provide an electrical riser diagram, NEC 230.9. Include underground service entrance conductors/conduit.
a. Show each meter and address/unit associated with each meter.
b. Show bus bar or equipment rating and AIC ratings of the new equipment.
c. Provide sizing and other info as needed to verify code compliance.

Additional comments may be forthcoming with corrected plans